Whoops Warren you made a mistake there.

 The  capacitors are  not fitted  to make  the meters  read correctly  but  to
correct  the  power  factor  and  so keep  the  current  lower  than  it would
be otherwise. The meters read the amount of power delivered no matter what the
phase angle of the current.

  You see these capacitors fitted  to fluoescent lamps to correct  the lagging
phase caused by  the ballast. Hhmmm,  as the voltage  drop accross a fluo lamp
is about 100 or so volts, do you use ballasts at all in the US ?

  If not how do you get them to start ?

 Anyway in large buildings etc there are special meters used that indicate the
degree of power factor on  the installation and increase the  electricity bill
to  compensate  for  the  extra current  carrying  capacitor  that  has to  be
provided.

  This extra charge has the effect of encouraging the customer to do something
about his power factor.

  Incidently, I  remember something  about using  an alternator as a motor and
over exciting the field winding and  so producing a leading phase angle and so
correcting the  phase angle  of the  whole works site.  From memory this was
done in the BHP steel works north of here at Newcastle.

  Anyone know about this technique ?

73 Barry VK2AAB