3 PHASE POWER
This is how AC power is normally generated & distributed, as it is more
efficient than other systems, except for DC that is the best, but very
difficult to transform.

The wire colour scheme may differ between countries & also the voltage!

The phase angle between phases is 120ø, because of this the voltages are added
up vectorialy so at first sight 2x 230v does not make 400v.

Line
   Red ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ           STAR LOADS               DELTA LOADS
(Brown)/³\  /³\       /³\               ³
       400v  |         |               Red                        Red
       \³/  400v       |               Load                        o
  Yel ÄÄÄÄÄÄÄÄÄÄÄÄ     |                ³                        /60ø\
(Black)/³\   |   /³\   |           120ø o 120ø               400v     400v
       400v  |    |    |             /     \               Load        Load
       \³/  \³/   |    |         Blue 120ø Yellow          / 60ø      60ø \
Blue ÄÄÄÄÄÄÄÄ     |    |      Load             Load      o______ 400v ______o
(Grey) /³\        |    |    /                     \    Blue      Load      Yel
       230v      230v 230v     If loads balanced               No Neutral
       \³/       \³/  \³/      centre = neutral &
Black ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ        loads all get 230v
(Blue)    (neutral)


NEW COLOUR HAZARDS !
New EU colours are Brown Black Grey for Lives & Blue Neutral
            replace Red Yellow Blue for Lives & Black Neutral. Green/Yel earth.

    N.B. the lethal change in use for both BLACK & BLUE colours!

Also note the colour layout of new 3 phase 4 core cable means, that a joint can
not be straight to an old cable & bigger joints casings will be needed to allow
for at least 2 cores to be bridged!  

Single phase will change from Red live, Black Neutral to Brown & Blue
respectifully. But highly confusing in a 3 phase board with both old black
wire loads for Neutrals & Black Bus feed for live! Brown & Blue sleeves are to
be used over Red & Black wires!

I can see many 230V loads being tested on 400V & several deaths from this
Red-Green blind safety change!


3 PHASE TRANSFORMERS
Like any transformer the voltage can be changed, or isolated etc. The
difference being that 3 legs of the transformer carry the windings rather than
just the middle. ÚÄÄÄÄÄÄÄÄÄÄÄ¿   The winding connections can be either STAR or
                 ³ ÚÄÄ¿ ÚÄÄ¿ ³   DELTA or combinations of both.
                ÚÁÄÁ¿ÚÁÄÁ¿ÚÁÄÁ¿  When cross connected star-delta a rotation of
      Windings->³ 1 ³³ 2 ³³ 3 ³  90øin phase occurs. (eg 30ø from other phases)
                ÀÂÄÂÙÀÂÄÂÙÀÂÄÂÙ               . 
      Laminated  ³ ÀÄÄÙ ÀÄÄÙ ³      |   or   / \   becomes   _ /  or   /'³
         Core  ->ÀÄÄÄÄÄÄÄÄÄÄÄÙ     / \      '---'              \      '\,³

(due to magneto striction audio the hum given off from the steel is 300Hz)


3 PHASE RECTIFICATION
With rectification 3 diodes gives about 30% ripple at 150Hz (3x supply) the
ripple is not much as singe phase, as some of the 120ø voltages overlap.
      ___________________
    _³_   _³_   _³_  /|\
    /_\   /_\   /_\   |         100% ´    _.-._   _.-._   _.-._  Â Ripple
R ÄÄÄÙ     ³     ³   RAW         70%_³   /     \ /     \ /       Á
           ³     ³    DC             ³  ³       ³       ³
Y ÄÄÄÄÄÄÄÄÄÙ     ³    |              ³ ³       ³ ³     ³ ³
                 ³    |              ³³       ³   ³   ³   ³
BÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÙ    |              ÅÄÄÄÄÄÄÄÄÂÄÄÄÂÄÄÄÂÄÄÄÂÄÄÄÂÄ
                     \³/             0ø      120 180 240 310 360ø
NÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ


3 PHASE BRIDGE RECTIFIERS
Only 6 diodes produce a 3 phase bridge & that gives about 14% @ 300Hz (6x
supply) ripple peak to peak, as more of the 60ø voltages overlap.
      ________________
    _³_   _³_   _³_                                           
    /_\   /_\   /_\         100% ´    _.-._.-._.-._.-._.-._  Â Ripple
R ÄÄÄ´     ³     ³          86% /³   /   / \ / \ / \ / \ /   ^
     ³     ³     ³               ³  ³   ³   ³   ³   ³   ³
Y ÄÄÄ)ÄÄÄÄÄ´     ³               ³ ³   ³   ³ ³ ³ ³ ³ ³ ³ ³
     ³     ³     ³               ³³   ³   ³   ³   ³   ³   ³
BÄÄÄÄ)ÄÄÄÄÄ)ÄÄÄÄÄ´               ÅÄÄÄÄÂÄÄÄÂÄÄÄÂÄÄÄÂÄÄÄÂÄÄÄÂÄ
    _³_   _³_   _³_              0ø  60  120 180 240 310 360ø
    /_\   /_\   /_\
     ÀÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄ


12 PHASE RECTIFIERS
With push pull or 3 phase bridge system, and using both star & delta windings
there can effectively be 12 lives that are only 30ø apart. Using 2x 3 phase
bridges or 12 winding & diodes the resultant ripple is only about 3.6% @ 600Hz,
assuming all the voltages are equal!

            _______________________
          _³_ _³_ _³_ _³_ _³_ _³_
Floating  /_\ /_\ /_\ /_\ /_\ /_\
  .   RDÄÄÄ´   ³   ³   ³   ³   ³    100% ´    _.-.-.-.-.-.-.-.-. = Ripple
 / \  YDÄÄÄ)ÄÄÄ´   ³   ³   ³   ³    96% /³   / / /\/\/\/\/\/\/\
'---' BDÄÄÄ)ÄÄÄ)ÄÄÄ´   ³   ³   ³         ³  ³ ³ ³ ³ ³ ³ ³ ³ ³ ³
Windings   ³   ³   ³   ³   ³   ³         ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³
      RSÄÄÄ)ÄÄÄ)ÄÄÄ)ÄÄÄ´   ³   ³         ³³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³
  |   YSÄÄÄ)ÄÄÄ)ÄÄÄ)ÄÄÄ)ÄÄÄ´   ³         ÅÄÄÂÄÂÄÄÄÂÄÄÄÂÄÄÄÂÄÄÄÂÄ
 / \  BSÄÄÄ)ÄÄÄ)ÄÄÄ)ÄÄÄ)ÄÄÄ)ÄÄÄ´        0ø 30 60 120 180 240 310ø
          _³_ _³_ _³_ _³_ _³_ _³_
          /_\ /_\ /_\ /_\ /_\ /_\
           ÀÄÄÄÁÄÄÄÁÄÄÄÁÄÄÄÁÄÄÄÁÄÄÄ



Why Don't U send an interesting bul?