By G8MNY (Updated Nov 03)
On 24cms ATV repeater GB3HV, we used the high current diode protectors from RS,
part No RS 239-494 (old part No now! so you will need other suppliers) which is
actually a special 15V zener diode, designed to always blow S/C when over-
powered, they can handle pulse currents of 75A. This was used even thought we
had a 30AH car battery connected as well, as we were worried about lightening
spikes to the mast on the hill top site.
THEY DID WORK
When our low voltage chopper PSU blew up some years ago, it put it's high
current 60V DC secondary rail out to the battery, blowing the series 30A bolted
in fuse, & applying 60V to all the 12V kit. The spike zeners did their job &
blew all the individual unit fuses. Only the odd unprotected control transistor
got zapped.
SINGLE BATTERY LOAD
FUSE FUSES
ÚÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÂÄoÄoÄÄÄÄÄÂÄ 1 PROTECTED
+³ o blown ÃÄoÄoÄÄÄÂÄ)Ä 2 LOADS
60V o 30A fuse ÀÄoÄoÄÂÄ)Ä)Ä 3
FAILED BATT ³ ³ ³
PSU ³ Z Z Z (RS 239-494)
ÀÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÁÄÁÄ
OLD FUSE ARRANEGMENT
This protection certainly saved 300 pounds of expensive 23cm silicon from
burning out!
40A 40A INDIVIDUAL
CHARGE CABLE LOAD
FUSE FUSE FUSES
ÚÄÄÄoÄoÄÂÄoÄoÄÄÄÄÄÄÄÄÂÄoÄoÄÄÄÄÄÂÄ 1 PROTECTED
+³ ³ ÃÄoÄoÄÄÄÂÄ)Ä 2 LOADS
PSU ³ ÀÄoÄoÄÂÄ)Ä)Ä 3
³ BATT ³ ³ ³
³ ³ Z Z Z (RS 239-494)
ÀÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÁÄÁÄ
NEW FUSE ARRANGEMENT
A different design SMPSU (2x 7V 40A in series) is now in use with extra fuses
so that there is a fuse between the PSU-Batt fuse, a another fuse battery to
load wiring, & individual unit fuses.